Integrated electronic motor and pump protection
- Enhanced Class 10 electronic overload protection
- Specifically designed for submersible motors
- Built-in 1.15 service factor compensation
- Underload (dry-run protection)
- Current phase unbalance protection
- Cycle fault protection
- Locked rotor and stall protection
Multi-voltage operating range with automation I/O
- Accepts 200-600 VAC directly, true plug and play
- Includes a dry contact auto-run input and fault relay output
Industrial grade construction
- Door mounted heavy-duty HOA switch
- Housed in an outdoor rated, gasketed, NEMA 3R enclosure
- NEMA/IEC rated magnetic contactors feature 2.5 million electrical cycles at full rated current
Optional circuit breaker disconnect (Service Entrance rated)
- UL 489 circuit breaker provides branch and short circuit protection
- No fuses required – saves time and money
- Lockable handle for safety
Revolutionary Motor Protection
- Aware: SMARTSTART™ protects your system from adverse dry-run conditions with built-in underload protection standard.
- Watchful: SMARTSTART™ detects harmful extended starting conditions with maximum time to start. Monitors motor in-rush current conditions and trips if the motor doesn’t start within 10 seconds (class 10 overload) regardless of FLA setting.
- Active: Active current monitoring provides superior protection against locked rotor and stall conditions, tripping faster than a standard inverse trip curve, regardless of the FLA setting.
-
NEMA 3R Enclosed Starter (With Service Entrance Circuit Breaker Disconnect)
Part Number 200 V - 460 V
3-Phase
Amp Range600 V
3-Phase
Amp Range3-Phase Max. Amps / HP 200 V - 230 V
1-Phase
Amp Range1-Phase Max. Amps / HP 200 V 230 V 460 V 600 V 230 V A HP** A HP** A HP** A HP** A HP** SSP3B-3A015S 6-8 6-8 8 2 8 2 8 5 8 5 6-8 8 1 SSP3B-3A020S 8-11 8-11 11 3 11 3 11 7.5 11 10 8-11 11 1.5 SSP3C-3A030S 12-17 12-17 17 3 17 3 17 10 17 15 12-17 17 3 SSP3C-3A040S 16-22 16-22 22 5 22 7.5 22 15 22 20 16-17 17 3 SSP3E-3A050S 20-28 20-28 28 7.5 28 10 28 20 28 25 20-28 28 5 SSP3E-3A060S 24-32 24-32 32 7.5 32 10 32 20 32 30 24-32 32 7.5 SSP3F-3A080S 32-45 32-45 45 10 45 15 45 30 45 40 32-45 45 7.5 SSP3F-3A100S 40-52 40-52 52 15 52 20 52 40 52 50 40-50 50 10 SSP3G-3A125S 50-71 50-71 71 20 71 25 71 50 71 60 50-68 68 15 SSP3H-3A150S 60-80 60-77 80 25 80 30 80 60 77 75 60-80 80 15 - 1 & 3 Phase, 50/60Hz, 200~600VAC
- *Standard Models not available in 1-Phase
- **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.
NEMA 3R Enclosed Starter (Disconnect not Included)
Part Number 200 V - 460 V
3-Phase
Amp Range600 V
3-Phase
Amp Range3-Phase Max. Amps / HP 200 V - 230 V
1-Phase
Amp Range1-Phase Max. Amps / HP 200 V 230 V 460 V 600 V 230 V A HP** A HP** A HP** A HP** A HP** SSP3E-30S 1-32 1-32 32 7.5 32 10 32 20 32 30 1-32 32 5 SSP3F-30S 22-52 22-52 52 15 52 15 52 40 52 50 22-50 50 10 SSP3H-30S 50-80 50-77 80 25 80 30 80 60 77 75 50-80 80 15 - Smartstart Pump Starter - 3-Phase, 50/60 Hz, 200~600 VAC
- *Standard Models not available in 1-Phase
- **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.
NEMA 1 Enclosed Starter (Disconnect not Included)
Part Number 200 V - 460 V
3-Phase
Amp Range600 V
3-Phase
Amp Range3-Phase Max. Amps / HP 200 V - 230 V
1-Phase
Amp Range1-Phase Max. Amps / HP 200 V 230 V 460 V 600 V 230 V A HP** A HP** A HP** A HP** A HP** SSP1E-30S 1-32 1-32 32 7.5 32 10 32 20 32 30 1-32 32 5 SSP1F-30S 22-52 22-52 52 15 52 15 52 40 52 50 22-50 50 10 SSP1H-30S 50-80 50-77 80 25 80 30 80 60 77 75 50-80 80 15 - Smartstart Pump Starter - 3-Phase, 50/60 Hz, 200~600 VAC
- *Standard Models not available in 1-Phase
- **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.
Factory Installable Options
Part Number Description SSP-HOA-KEY Keyed HOA Switch SSP-RPL Run Pilot Light SSP-FPL Fault Pilot Light SSP-SRG-240V Surge Suppressor, 200/230V SSP-SRG-460V Surge Suppressor, 460V SSP-SRG-600V Surge Suppressor, 600V SSP-2FC 2-Float Switch Input Terminals SSP-3FC 3-Float Switch Input Terminals SSP-CAM-KEY Keyed Enclosure Latch SSP-CAM-PAD Padlockable Enclosure Latch SSP-DHM Digital Hour Meter SSP-RLY-120VAC Interposing Run Relay - 120V SSP-RLY-24VAC-DC Interposing RunRelay - 24V SSP-1PH Wiring for Single Phase Input - Factory Installable Options apply to configured-to-order models only and are subject to variable lead times. Consult your Franklin Electric Representative.
NEMA 3R Dimensions
Smartstart Pump Starter Starter Type Dimensions Mounting H W D Hardware Size Spacing (Height x Width) SSP3B-3A015S with Service Entrance
Circuit Breaker Disconnect22 15 10 5/16" 17 & 5/8 x 12 & 3/4 SSP3B-3A020S SSP3C-3A030S SSP3C-3A040S SSP3E-3A050S SSP3E-3A060S SSP3F-3A080S SSP3F-3A100S SSP3G-3A125S with Service Entrance
Circuit Breaker Disconnect32 15 10 5/16" 27 & 5/8 x 12 & 3/4 SSP3H-3A150S SSP3E-30S Disconnect not Included 16 12 10 5/16" 13 x 9 & 1/2 SSP3F-30S SSP3H-30S - *All measurements shown in inches
NEMA 1 Dimensions
Smartstart Pump Starter Starter Type Dimensions Mounting H W D Hardware Size Spacing (Height x Width) SSP1E-30S Disconnect not Included 16 7.5 6 1/4" 15 x 5 & 1/4 SSP1F-30S SSP1H-30S Disconnect not Included 16 12 8 5/16" 13 x 9 & 1/2 - *All measurements shown in inches
-
Starter Type Full Voltage, Non-Reversing With or Without Service Entrance Rated Circuit Breaker Disconnect (NEMA 3R Models Only) Enclosure Options NEMA Type 1 Enclosed - Indoor NEMA Type 3R Enclosed - Rain Tight *NEMA Type 4 Enclosed - Washdown Rated *NEMA Type 4X Fiberglass - Washdown Rated, Corrosion Resistant User Interface Control - NEMA 1 Hand-Off-Auto Keypad with LED's for Hand, Off, Auto,Run, and Fault Indication Control - NEMA 3R, 4 & 4X Hand-Off-Auto Switch Setting Adjustments Internal dial for motor FLA/SFA setting, Internal dial for Underload % setting Inputs/Outputs Inputs Auto-Run Input D1/D2 Terminal, Normally Open Dry Contact, when closed, the motor will start when in auto mode Output Fault Relay Output O1/O2 Terminal, Normally Open Relay - Rated for 12-240V, closes when a fault is detected Contactor Power Supplied power to the contactor C+/C- Terminal, For Use with Franklin Electric Contactors Only Environmental Ambient Operating Temp -5 °F to 140 °F (-20 °C to 60 °C) Ambient Storage Temp -5 °F to 185 °F (-20 °C to 85 °C) Relative Humidity 5% to 95% non-condensing Overload Operational Specifications Overload Type Electronic I2T trip curve Overload Trip Class Class S (submersible) Overload Setting Range SSP[ ]B to SSP[ ]E 1-32A SSP[ ]F 22-52A SSP[ ]G to SSP[ ]H 50-80A Current Phase Unbalance Trips when current deviation
is greater than the selected value.25% (OFF) or 80% (ON). Dip Switch Selectable Fault Reset NEMA 1 Manual, Hold Off Key for 5 Seconds NEMA 3R, 4, 4X Manual, Place Hand-Off-Auto Switch in the Off Position for 5 Seconds Underload (Dry Well) Protection Adjustable Trip: 0%-100% of FLA 70% Default Motor Stall Trips within 0.5 seconds (disabled during startup) Rapid Start (Cycle) Fault Trip if cycle rate exceeds 20 starts/minute Max Time to Start If starting current is outside of an acceptable range (in-rush / 5) and still decreasing after 10 seconds Power Fail Modes Selectable: Return to Off Mode or return to last mode prior to power fail (Hand, Off, or Auto) Agency Approvals UL/cUL, CSA, CE - *Options apply to configured-to-order models only and are subject to variable lead times. Consult your Franklin Electric Representative.
-