Smartstart Pump Starter

Smartstart Pump Starter

3Ø, 50/60 Hz, 200~600 VAC, 1-130 FLA (Differs per model)

FE Select Black Logo

FE Select - Configure & Quote

USA Canada
Features
Order Info
Specifications
Resources
  • Integrated electronic motor and pump protection

    • Enhanced Class 10 electronic overload protection
    • Specifically designed for submersible motors
    • Built-in 1.15 service factor compensation
    • Underload (dry-run protection)
    • Current phase unbalance protection
    • Cycle fault protection
    • Locked rotor and stall protection

    Multi-voltage operating range with automation I/O

    • Accepts 200-600 VAC directly, true plug and play
    • Includes a dry contact auto-run input and fault relay output

    Industrial grade construction

    • Door mounted heavy-duty HOA switch
    • Housed in an outdoor rated, gasketed, NEMA 3R enclosure
    • NEMA/IEC rated magnetic contactors feature 2.5 million electrical cycles at full rated current

    Optional circuit breaker disconnect (Service Entrance rated)

    • UL 489 circuit breaker provides branch and short circuit protection
    • No fuses required – saves time and money
    • Lockable handle for safety

    Revolutionary Motor Protection

    • Aware: SMARTSTART™ protects your system from adverse dry-run conditions with built-in underload protection standard.
    • Watchful: SMARTSTART™ detects harmful extended starting conditions with maximum time to start. Monitors motor in-rush current conditions and trips if the motor doesn’t start within 10 seconds (class 10 overload) regardless of FLA setting.
    • Active: Active current monitoring provides superior protection against locked rotor and stall conditions, tripping faster than a standard inverse trip curve, regardless of the FLA setting.
  • NEMA 3R Enclosed Starter (With Service Entrance Circuit Breaker Disconnect)

    Part Number200 V - 460 V
    3-Phase
    Amp Range
    600 V
    3-Phase
    Amp Range
    3-Phase Max. Amps / HP200 V - 230 V
    1-Phase
    Amp Range
    1-Phase Max. Amps / HP
    200 V230 V460 V600 V230 V
    AHP**AHP**AHP**AHP**AHP**
    SSP3B-3A015S6-86-8828285856-881
    SSP3B-3A020S8-118-11113113117.511108-11111.5
    SSP3C-3A030S12-1712-171731731710171512-17173
    SSP3C-3A040S16-2216-22225227.52215222016-17173
    SSP3E-3A050S20-2820-28287.528102820282520-28285
    SSP3E-3A060S24-3224-32327.532103220323024-32327.5
    SSP3F-3A080S32-4532-45451045154530454032-45457.5
    SSP3F-3A100S40-5240-52521552205240525040-505010
    SSP3G-3A125S50-7150-71712071257150716050-686815
    SSP3H-3A150S60-8060-77802580308060777560-808015
    • 1 & 3 Phase, 50/60Hz, 200~600VAC
    • *Standard Models not available in 1-Phase
    • **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.

    NEMA 3R Enclosed Starter (Disconnect not Included)

    Part Number200 V - 460 V
    3-Phase
    Amp Range
    600 V
    3-Phase
    Amp Range
    3-Phase Max. Amps / HP200 V - 230 V
    1-Phase
    Amp Range
    1-Phase Max. Amps / HP
    200 V230 V460 V600 V230 V
    AHP**AHP**AHP**AHP**AHP**
    SSP3E-30S1-321-32327.53210322032301-32325
    SSP3F-30S22-5222-52521552155240525022-505010
    SSP3H-30S50-8050-77802580308060777550-808015
    • Smartstart Pump Starter - 3-Phase, 50/60 Hz, 200~600 VAC
    • *Standard Models not available in 1-Phase
    • **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.

    NEMA 1 Enclosed Starter (Disconnect not Included)

    Part Number200 V - 460 V
    3-Phase
    Amp Range
    600 V
    3-Phase
    Amp Range
    3-Phase Max. Amps / HP200 V - 230 V
    1-Phase
    Amp Range
    1-Phase Max. Amps / HP
    200 V230 V460 V600 V230 V
    AHP**AHP**AHP**AHP**AHP**
    SSP1E-30S1-321-32327.53210322032301-32325
    SSP1F-30S22-5222-52521552155240525022-505010
    SSP1H-30S50-8050-77802580308060777550-808015
    • Smartstart Pump Starter - 3-Phase, 50/60 Hz, 200~600 VAC
    • *Standard Models not available in 1-Phase
    • **HP rating is based on standard NEMA B, 4-pole motor design as represented in NEC table 430.150 full-load current, 3-phase alternating current motors.

    Factory Installable Options

    Part NumberDescription
    SSP-HOA-KEYKeyed HOA Switch
    SSP-RPLRun Pilot Light
    SSP-FPLFault Pilot Light
    SSP-SRG-240VSurge Suppressor, 200/230V
    SSP-SRG-460VSurge Suppressor, 460V
    SSP-SRG-600VSurge Suppressor, 600V
    SSP-2FC2-Float Switch Input Terminals
    SSP-3FC3-Float Switch Input Terminals
    SSP-CAM-KEYKeyed Enclosure Latch
    SSP-CAM-PADPadlockable Enclosure Latch
    SSP-DHMDigital Hour Meter
    SSP-RLY-120VACInterposing Run Relay - 120V
    SSP-RLY-24VAC-DCInterposing RunRelay - 24V
    SSP-1PHWiring for Single Phase Input
    • Factory Installable Options apply to configured-to-order models only and are subject to variable lead times. Consult your Franklin Electric Representative.

    NEMA 3R Dimensions

    Smartstart Pump StarterStarter TypeDimensionsMounting
    HWDHardware SizeSpacing (Height x Width)
    SSP3B-3A015Swith Service Entrance
    Circuit Breaker Disconnect
    2215105/16"17 & 5/8 x 12 & 3/4
    SSP3B-3A020S
    SSP3C-3A030S
    SSP3C-3A040S
    SSP3E-3A050S
    SSP3E-3A060S
    SSP3F-3A080S
    SSP3F-3A100S
    SSP3G-3A125Swith Service Entrance
    Circuit Breaker Disconnect
    3215105/16"27 & 5/8 x 12 & 3/4
    SSP3H-3A150S
    SSP3E-30SDisconnect not Included1612105/16"13 x 9 & 1/2
    SSP3F-30S
    SSP3H-30S
    • *All measurements shown in inches

    NEMA 1 Dimensions

    Smartstart Pump StarterStarter TypeDimensionsMounting
    HWDHardware SizeSpacing (Height x Width)
    SSP1E-30SDisconnect not Included167.561/4"15 x 5 & 1/4
    SSP1F-30S
    SSP1H-30SDisconnect not Included161285/16"13 x 9 & 1/2
    • *All measurements shown in inches
  • Starter Type
    Full Voltage, Non-Reversing
    With or Without Service Entrance Rated Circuit Breaker Disconnect (NEMA 3R Models Only)
    Enclosure Options
    NEMA Type 1 Enclosed - Indoor
    NEMA Type 3R Enclosed - Rain Tight
    *NEMA Type 4 Enclosed - Washdown Rated
    *NEMA Type 4X Fiberglass - Washdown Rated, Corrosion Resistant
    User Interface
    Control - NEMA 1Hand-Off-Auto Keypad with LED's for Hand, Off, Auto,Run, and Fault Indication
    Control - NEMA 3R, 4 & 4XHand-Off-Auto Switch
    Setting AdjustmentsInternal dial for motor FLA/SFA setting, Internal dial for Underload % setting
    Inputs/Outputs
    InputsAuto-Run InputD1/D2 Terminal, Normally Open Dry Contact, when closed, the motor will start when in auto mode
    OutputFault Relay OutputO1/O2 Terminal, Normally Open Relay - Rated for 12-240V, closes when a fault is detected
    Contactor PowerSupplied power to the contactorC+/C- Terminal, For Use with Franklin Electric Contactors Only
    Environmental
    Ambient Operating Temp -5 °F to 140 °F (-20 °C to 60 °C)
    Ambient Storage Temp -5 °F to 185 °F (-20 °C to 85 °C)
    Relative Humidity 5% to 95% non-condensing
    Overload Operational Specifications
    Overload TypeElectronic I2T trip curve
    Overload Trip ClassClass S (submersible)
    Overload Setting RangeSSP[ ]B to SSP[ ]E1-32A
    SSP[ ]F22-52A
    SSP[ ]G to SSP[ ]H50-80A
    Current Phase UnbalanceTrips when current deviation
    is greater than the selected value.
    25% (OFF) or 80% (ON). Dip Switch Selectable
    Fault ResetNEMA 1Manual, Hold Off Key for 5 Seconds
    NEMA 3R, 4, 4XManual, Place Hand-Off-Auto Switch in the Off Position for 5 Seconds
    Underload (Dry Well) ProtectionAdjustable Trip: 0%-100% of FLA70% Default
    Motor StallTrips within 0.5 seconds (disabled during startup)
    Rapid Start (Cycle) FaultTrip if cycle rate exceeds 20 starts/minute
    Max Time to StartIf starting current is outside of an acceptable range (in-rush / 5) and still decreasing after 10 seconds
    Power Fail ModesSelectable: Return to Off Mode or return to last mode prior to power fail (Hand, Off, or Auto)
    Agency ApprovalsUL/cUL, CSA, CE
    • *Options apply to configured-to-order models only and are subject to variable lead times. Consult your Franklin Electric Representative.